dc.creator | ALMEIDA, Clovis Andrade de | - |
dc.contributor.advisor1 | BARBOSA, Daniel | - |
dc.contributor.referee1 | FREIRE, Kleber | - |
dc.contributor.referee2 | ARAUJO, Renato José Pino de | - |
dc.date.accessioned | 2017-07-11T22:35:29Z | - |
dc.date.issued | 2014-09-18 | - |
dc.identifier.citation | ALMEIDA, Clovis Andrade de. Distorção harmônica: estudo de caso de uma central telefônica. 2014. 104p. Dissertação (Regulação da Indústria e Energia) - UNIFACS Universidade Salvador, Salvador, 2014. | por |
dc.identifier.uri | http://teste.tede.unifacs.br:8080/tede/handle/tede/509 | - |
dc.description.resumo | Este trabalho apresenta um estudo sobre a distorção harmônica que ocorre em uma Central Telefônica, sobre o sistema de geração própria, causado por cargas não lineares, particularmente o conversor CA-CA. Foram considerados como aspectos relevantes para a escolha do tema a preocupação das concessionárias de energia e dos consumidores com a qualidade do fornecimento. No que tange a um sistema telefônico, adicionalmente às perdas conhecidas por efeito Joule torna-se importante o controle das distorções associadas a eventuais interferências eletromagnéticas. Dentro do contexto teórico, são apresentados resumos de estudos já realizados sobre as distorções harmônicas, alguns dos quais com propostas de soluções. Não obstante, não foram encontrados estudos sobre componentes harmônicos das correntes em sistemas de geração própria de centrais telefônicas, razão pela qual surgiu a motivação para a realização da análise da distorção e as possíveis consequências nos equipamentos eletrônicos de uma empresa telefônica de grande porte. São mostrados os resultados de pesquisas de campo com estudo comparativo entre o conteúdo harmônico associado à rede da concessionária de energia e o associado ao sistema de geração própria. Finalmente, são apresentadas propostas não somente para aprofundamento das pesquisas como também para reduzir o impacto de aumento das distorções pelo esperado aumento da quantidade de cargas não lineares, as quais incluem a inserção de filtros passivos trifásicos que se mostraram viáveis conforme simulações feitas com MATLAB. | por |
dc.description.abstract | This work presents a study on the harmonic distortion that occurs in a telephone system on the self-generation system, caused by non-linear loads, particularly the AC-AC converter. The concern of utilities and consumers with the quality of power supply were considered to be relevant to the choice of theme. With respect to a telephone system and in addition to losses known as Joule effect, it becomes important to control the distortions associated with any electromagnetic interference. Within the theoretical context, study summaries already made on the harmonic distortions, some with proposed solutions are presented. However, there are no studies on harmonic components of current in self-generation of telephone exchanges systems. That is the reason of the motivation to carry out the analysis of distortion and its possible consequences on the equipments of a large telephone company. Results of the field research are shown with a comparative study of the harmonic content associated with the power utility and the associated self-generation system. Finally, proposals are made not only to deepen the research but also to reduce the impact of increased distortions by the expected increase in the amount of non-linear loads, which include the implementation of three-phase passive filters that were viable as simulations with MATLAB. | eng |
dc.description.provenance | Submitted by Roseli Araujo ([email protected]) on 2017-07-11T22:35:29Z No. of bitstreams: 1 Dissertação ABNT CLOVIS ANDRADE DE ALMEIDA.pdf: 2486312 bytes, checksum: 6677d55f5a4a87b74538a0a100d599e9 (MD5) | eng |
dc.description.provenance | Made available in DSpace on 2017-07-11T22:35:29Z (GMT). No. of bitstreams: 1 Dissertação ABNT CLOVIS ANDRADE DE ALMEIDA.pdf: 2486312 bytes, checksum: 6677d55f5a4a87b74538a0a100d599e9 (MD5) Previous issue date: 2014-09-18 | eng |
dc.format | application/pdf | * |
dc.language | por | por |
dc.publisher | Universidade Salvador | por |
dc.publisher.department | Regulação da Indústria e Energia | por |
dc.publisher.country | Brasil | por |
dc.publisher.initials | UNIFACS | por |
dc.publisher.program | Regulação da Indústria e Energia | por |
dc.rights | Acesso Aberto | por |
dc.subject | Central telefônica | por |
dc.subject | Geração própria | por |
dc.subject | Cargas não lineares | por |
dc.subject | Filtros trifásicos | por |
dc.subject.cnpq | Engenharia | por |
dc.title | Distorção harmônica: estudo de caso de uma central telefônica | por |
dc.type | Dissertação | por |
Aparece nas coleções: | Regulação da Industria de Energia |
Arquivos associados a este item:
Arquivo | Descrição | Tamanho | Formato | |
---|---|---|---|---|
Dissertação ABNT CLOVIS ANDRADE DE ALMEIDA.pdf | Dissertação ABNT CLOVIS ANDRADE DE ALMEIDA | 2,43 MB | Adobe PDF | Baixar/Abrir Pré-Visualizar |
Os itens no repositório estão protegidos por copyright, com todos os direitos reservados, salvo quando é indicado o contrário.